2 Operating A&D DataManagement 07/2011
2.4 Specifying the properties of the control components
© Siemens AG 2011 All Rights Reserved
2-62 SIMATIC A&D DataManagement Client - 07/2011
• Drive A – Drive B
The Simodrive 611 Universal drive can be supplied with either one or two
axes on a module. On modules with two axes, these axes are
distinguished by being named drive A and drive B. This can be set in
ADDM.
• Routing via agent
With this setting the drive is connectable via a network computer with
ADDM-Agent. For this the name or the TCP/IP address of the computer
has to be declared.
• RS-232 / RS-485
The 611U and 611UE drives are loaded, compared and backed up via the
RS-232 / RS-485. The COM1/2 interface of the backup computer has to be
set. The transfer may also be made over the PROFIBUS with an optional
expansion module.
• PROFIBUS
When the PROFIBUS is used as a transmission route, the coupling to the
drive may be made in various ways.
If the backup computer is connected directly to the PROFIBUS segment of
the drives (direct connection), the PROFIBUS address set for the drive
must be stated in order to gain access.
If the backup computer is connected via a SIMATIC S7 or a higher-level
PROFIBUS segment (routed via S7 CPU), the subnet ID of the network
segment and the MPI address of the S7 CPU must be stated. In the
STEP7 project, the subnet ID information can be queried via the SIMATIC
Manager.
• Multi-backup
This option enables the user to store up to 99 memory dumps of the
component. The number is specified in Max. no. of backups, also see
subsection 2.4.1 and subsection 2.6.2.
• Parameter file
In ADDM, the button for selecting the parameter file sets a pointer to the
drive start up data. Actuating the button opens a browser for navigating to
the drive data. The data is generated and stored with the SimoComU/A
software package.